- Overview
- Product Description
- Product Parameters
- Detailed Photos
- Packaging & Shipping
- Our Advantages
Basic Info.
Model NO.
GN30-12D/ (1600-3150)-40
Operation
Manual
Grounding Mode
Grounding
Movement Mode
Plug-in Type
Number of Poles
Three Pole
Grounding
Double Ground
Series
Three
Run
Turn the Horizontal
Switching Mode
Double-Throw Type
Common Model
Jn15
Structure of Operating
Electric
Certification
ISO, GS, RoHS, CE, IS9001
Brand
Mingzhe
Protection
Overvoltage,Overload,Overtemperature
Rated Voltage
24kv 12kv
Rating Frequency
50Hz
Types
Earthing Switch
Transport Package
Carton
Specification
30*30*50cm
Trademark
MINGZHE
Origin
China
HS Code
8535299000
Production Capacity
2000PCS/Week
Product Description
GN30-12(D) series Indoor high voltage disconnecting switches is a new type of touch rotating knife isolator , which special designed for XGN2-12 HV switchgear, with rated voltage 12kV and three phase AC 50Hz indoor device. It's mainly used for making and breaking circuit under with voltage and no load.
Its main structure in three-phase chassis of the upper and lower two plane, fixed two set of insulator and contact, by rotating contactor, so as to realize switching on & off.Environment condition
- Ambient temperature: max. +40°C min. -25°C
- Altitude: ≤1000m
- Wind pressure: ≤700Pa (equals to wind speed 34m/s)
- Relative humidity: daily average ≤95%, monthly average ≤90%
- Earthquake intensity: ≤8 degree
- No corrosive, explosive or flammable gas ,no violent vibration
Technical Data
Model | GN30-12/ 400-12.5 | GN30-12/ 630-20 | GN30-12/ 1000-31.5 | GN30-12/ 1250-31.5 | GN30-12/ (1600-3150)-40 | |
GN30-12D/ 400-12.5 | GN30-12D/ 630-20 | GN30-12D/ 1000-31.5 | GN30-12D/ 1250-31.5 | GN30-12D/ (1600-3150)-40 | ||
Rated voltage (kV) | 12 | |||||
Rated current (A) | 400 | 630 | 1000 | 1250 | 1600-3150 | |
Rated short-time withstand current (kA) | 12.5 | 20 | 31.5 | 40 | ||
Rated short-circuit duration (s) | 4 | |||||
Rated peak withstand current (kA) | 31.5 | 50 | 80 | 100 | ||
Rated insulating level | 1min. PF withstand voltage (kV) | phase to phase/ to earth: 42, across open contacts: 49 | ||||
Lightning impulse withstand voltage (kV) | phase to phase/ to earth: 75, across open contacts: 85 |