Basic Info.
Model NO.
BYB1-63
Origin
China
HS Code
8536200000
Production Capacity
300000PCS/Year
Product Description
BYB1LE-63 series Residual current circuit breaker(without over-current protection) is suitable for the line of A and S 50/60Hz, voltage 240V(2pole)/415V(4pole), rated current up to 100A. When there is human electricity shock or if the leakage current of the line exceeds the prescribed value, it will cut off the power rapidly to protect human safety and prevent the accident due to the current leakage. It can be used as infrequent changeover of the line in normal situation. It is applicable to industrial site, commercial site, tall building and civil house.
It complies with standard of IEC/EN61008.1 and GB16916.1.
Each phase of conductor at the circuit breaker passes through the zero-sequence current transformer, and the secondary side of coil connects with the electromagnetic tripper. Under normal condition, the vector sum of each phase of current passing through zero-sequence current transformer is zero. The flux of the zero-sequence current transformer is zero. And the secondary output voltage is zero and the circuit breaker doesn't zero, and the zero-sequence current transformer would produce the magnetic flux, and the secondary side of coil would output the voltage. Once the leak current increases to drive the output voltage at the secondary side to grow to certain level, the electromagnetic release would activate to drive the operation mechanism to act to break the contact that connects the power, finally to realize the leak protection.
lectrical features | |
Type(an aware form of the earth leakage sensed) | B |
Rated current In | 25,40,63A |
Poles | 2P 4P |
Number of poles versus modules | 2P= 4mod;4P=4 mod |
Rated voltage Ue | 2P:230V~ 4P:400V~ |
Insulation voltage UI | 500V |
Rated frequency | 50/60Hz |
Rated sensitivity IAn | 0.03A 0.1A 0.3A |
Rated residual making and breaking capacity Im | 500(In=25-40A)630(In=63A) |
Short-circuit current lnc=lAc | 10000A |
SCPD fuse | 10000 |
Break time under IAn | ≤0.1S |
Rated impulse withstand voltage(1.2/50)Uimp | 6000V |
Dielectric test voltage at and ind.Freq.for 1min | 2.5kV |
Electrical life and Mechanical life | 4000 |
Pollution degree | 2 |
Installation | |
Fault current indicator | NO |
Protection degree | IP20 |
Ambient temperature(with a daily average of 35 ) | -5~+40°ºC |
Storage temperature | -25+70ºC |
Terminal connection type | Cable/U-type busbar/Pin -type busbar |
Terminal size top/bottom for cable | 35mm² 18-3 |
Tightening torque | 3.5N*m 22 |
Mounting | On DIN rail FN 60715 (35mm)by means of the fast clip device |
Connection | From top |