Basic Info.
Model NO.
LY1-C40/3S PV
Iimp
6.25ka(10/350us)
up
3.6ka
OEM Service
Yes
Delivery Way
FedEx, DHL, UPS, Aramex,EMS
Lead Time
3-5 Days
Transport Package
50PCS/CTN
Specification
41x22x31cm
Trademark
LEEYEE
Origin
China
HS Code
8536300000
Production Capacity
50000PCS/Month
Packaging & Delivery
Package Size
9.00cm * 8.00cm * 7.00cm
Package Gross Weight
1.000kg
Product Description
Product Description
Application
This T1+T2 DC spd surge protective device is applied low voltage standard IEC EN 61643-33 to protect against DC power line system and other equipment from over voltage and instantaneous over voltage damage. Widely used in photovoltaic comber box, power inverter, DC distribution cabinet etc. It has advantages of large discharge current, fast respond time, low residual voltage.The max. PV voltage up to UCPV ≤1500V dc. Features
1. Prewired complete unit consisting of a base part and plug-in protection modules
2. High discharge capacity due to heavy duty zinc oxide varistors
3. High reliability due to 'temperature-controlled' SPD monitoring device
2. High discharge capacity due to heavy duty zinc oxide varistors
3. High reliability due to 'temperature-controlled' SPD monitoring device
4 .Din rail installation, easy to install.
5. Inside over-current, over-heat, temperature control open circuit.
6. Fast response time, low residual voltage.
7. Window color indicates working condition, green means normal, red means fault.
5. Inside over-current, over-heat, temperature control open circuit.
6. Fast response time, low residual voltage.
7. Window color indicates working condition, green means normal, red means fault.
8. Class I II T1+2 protection degree.
Installation position
The cross-sectional area of ground wire should not be less than 4 mm2, and the length of total lead not more than 0.5m.
0.5MM
The minimum distance from any earthed conductive surface at which the SPD can be installed is 8mm.
Connection of remote signalling alarm: the SPD is provided with remote signalling interfaces (NC, COM and NO, normally closed), applicable for remote centralized monitoring or alarm. After the connection, check if the module is fitted in. If so, NC and COM are closed; if not, repress the module.
Model | LY1-C40PV |
SPD according to EN 61643-11 / IEC 61643-11 | Type 1+2 / class I+II |
Max. continuous operating pv. voltage Uc | 1000V DC |
Nominal discharge current (8/20μs) In | 20kA |
Maximum discharge current (8/20μs) Imax | 40kA |
Maximum impulse current (10/350μs) Iimp | 6.25 kA |
Impulse current totally (10/350μs) Iimp | 12.5kA |
Voltage protection level Up | 3.6 kV |
Follow current extinguishing capability [N-PE] Ifi | 100Arms |
Response time tA | 25ns (L-N) |
Matched fuse or circuit breaker | 32A |
Operating state / fault indication | Green ok / Red defect |
Cross-sectional area (min.) | 1.5 mm2 solid /flexible |
Cross-sectional area (max.) | 35 mm2 stranded / 25 mm2 flexible |
For mounting on | 35 mm DIN rail acc. to EN 60715 |
Switching capacity | AC:250V/0.5A DC:250V/0.1A,125V/0.2A,75V/0.5A |
Remote signalling alarming mode | Normal: closed; Failure: open-circuit |