LCD Touch Screen Transformer Oil Dielectric Strength Tester Breakdown Voltage Tester

Get accurate and reliable breakdown voltage testing with our LCD Touch Screen Transformer Oil Dielectric Strength Tester. Factory direct prices. Order now!
Request a Quote

PRODUCTS DETAILS

Basic Info.

Model NO.
GDYJ-502A
Control
Manual Control
Weight
45kg
Power Source
AC220V
Oil Cylinder Position
Top
Apparatus
Insulating Oil Dielectric Strength Tester
Application
LCD Insulating Oil Breakdown Voltage Tester
Function
Insulating Oil Breakdown Voltage Tester
Device
Oil Dielectric Withstanding Voltage Tester
Output Voltage
AC 0V~100kv
Max Test Times
9
Init Wait Times
0~999s
Stir Time
0~999s
Storage
100 Groups
Feature
All The Selection Can Be Done by Touch Panel
Transport Package
Plywood Case
Specification
490*410*450mm
Trademark
GOLD
Origin
Chongqing, China
HS Code
9031809090
Production Capacity
200PCS/Month

Product Description

LCD Touch Screen Transformer Oil Dielectric Strength Tester Breakdown Voltage Tester

LCD Touch Screen Transformer Oil Dielectric Strength Tester Breakdown Voltage Tester


Introduction:
  • It is developed according to IEC156 Insulating Oil Dielectric Strength Testing Method;

  • The oil test vessel with temperature measurement unit, so it can detect oil temperature.

  • With 8 Kinds of test mode as optional: IEC156, IS6792, BS5874, ASTM D1816 , ASTM D877, Proof test, 5 minutes standard test, Manual test;

  • It has large LCD display, all the selection can be done by touch panel with color LCD;

  • It also with micro-printer and can store 100 groups data, test data can also be unload to PC and output word report automatically;

  • It is multi-functional, stable, and easy for operation  

      

Functions:
LCD Touch Screen Transformer Oil Dielectric Strength Tester Breakdown Voltage Tester
1 IEC60156/IS6792/BS5874/VDE0370-5
2 User-defined
3 5 minute test
4 ASTMD877
5 ASTMD1816
6 JIS C 2101-99(S)
7 Proof "A"
8 Proof "B"

Specifications:
 
 
1 AC220V±10% power supply input
2 Output voltage: AC 0V~100KV  
3 Rate of voltage rise: 0.5kv/s±10%, 2kv/s±5%, 3kv/s±5%,5kv/s±5%
4 Max test times: 9
5 Init wait times:0~999s
6 Stir time: 0~999s
7 Wait time: 0~999s
8 Measurement accuracy: ±(1% of full scale + 2 digits) Resolution:0.1KV
9 Temperature measurement:
Measurement range : 0°C to 70°C, or better
Temperature resolution : 1°C, or better
Operating temperature : up to 45°C
10 Storage:100 groups
11 7 inch colorful LCD with touch pad
12 Oil test vessel temperature measurement unit


GDYJ Series Transformer Oil Dielectric Strength Tester Breakdown Voltage Tester:
   
Model GDYJ-501 GDYJ-502 GDYJ-502A
 
 
LCD Touch Screen Transformer Oil Dielectric Strength Tester Breakdown Voltage Tester
 
LCD Touch Screen Transformer Oil Dielectric Strength Tester Breakdown Voltage Tester
 
LCD Touch Screen Transformer Oil Dielectric Strength Tester Breakdown Voltage Tester
Output Voltage AC 0~80KV/0~100KV AC 0~100KV AC 0~80KV/0~100KV
Rate of Voltage Rise 2KV/s±10% 0.5/2/3/5 KV/s±5% 0.5/2/3/5 KV/s±5%
Max. Time Setting 0~9mins 9mins 0~99 seconds
Test Precision 3% RDG+0.3%FS 3% RDG+0.3%FS 1% of full scale +2digits
Max. Data Storage 100 groups 100 groups 100 groups
Power Supply AC220V±10% 50/60Hz AC220V±10% 50/60Hz AC220V±10% 50/60Hz
Environment Temp. 0~50Centigrade 0~50Centigrade 0~50Centigrade
Related Humidity <80%RH <80%RH <80%RH
Dimension 420*380*410mm 620*430*330mm 490*410*450mm
Weight 28kg 41kg 45kg

Contact us