- Overview
- Product Description
- Company Profile
Basic Info.
Model NO.
YCW1
Product Keywords
4p Draw out Type Air Circuit Beaker
Frequency(Hz)
50
Poles
3p/4p
Transport Package
CNC Packingstandard Packaging
Trademark
CNC
Origin
Zhejiang, China
Production Capacity
80000 Unit/Units Per Week
Product Description
OEM Factory 4p Draw out Type Air Circuit Beaker 3p Fixed Acb 3 Poles 5000A Breaker
YCW1 series intelligent air circuit breakers (hereinafter called ACB) are applied for the network circuit of AC 50Hz, rated voltage 400V, 690V and rated current between 630A and 6300A. Mainly used for distributing energy and protecting the circuit and power supply device against short-circuit, undervoltage, single-phase ground fault, etc. The ACB has intelligent protection function and the key parts adopt intelligent release. The release can make the accurate selective protection, which can avoid cutting off the power and improve the reliability of power supply.The products conform with IEC60947-1,IEC60947-2 standards.
YCW1-1000 series intelligent air circuit breakers(hereinafter called ACB) are applied for the network circuit of AC 50Hz,rated voltage 400V,690V and rated current up to 1000A.Mainly used for distributing energy and protecting the circuit and power supply device against short-circuit,undervoltage,single-phase ground fault etc. The ACB have intelligent protection function and the key parts adopt intelligent release. The release can make the accurate selective protection, which can avoid cutting off the power and improve the reliability of power supply.
The products confirm with IEC60947-2,GB14048.2.
Type | YCW1-2000 | YCW1-3200 | YCW1-6300 | ||
Pole | 3P, 4P | 3P, 4P | 3P, 4P | ||
Using category | B | B | B | ||
Rated current In | A | 630, 800, 1000 1250, 1600, 2000 | 2000, 2500, 3000 | 4000, 5000, 6300 | |
Rated frequency | Hz | 50 | 50 | 50 | |
Rated operation voltage Ue | V | 400, 690 | 400, 690 | 400, 690 | |
Rated insulation voltage Ui | V | 800 | 800 | 800 | |
Arcing distance | mm | 0 | 0 | 0 | |
Rated impulse withstanding voltage Uimp | V | 8000 | 8000 | 8000 | |
Rated operation short circuit breaking capacity Ics (O-t-CO) | 400V | kA | 40 | 65 | 100 |
660V | kA | 40 | 50 | 65 | |
Rated limiting short circuit breaking capacity Icu (O-t-CO) | 400V | kA | 65 | 80 | 120 |
660V | kA | 50 | 65 | 75 | |
Rated short time withstanding current Icw (O-t-CO, AC400V 0.4S) | 400V | kA | 40 | 50 | 80 |
Operation life | Per hour | times | 20 | 20 | 10 |
Electrical | times | 1000 | 500 | 500 | |
Mechanical | times | 10000 | 5000 | 5000 | |
Full breaking time | ms | 20~30 | 20~30 | 20~30 | |
Full closing time | ms | 55~70 | 55~70 | 55~70 | |
Power consumption | 3P | W | 360 | 1200 | 2000 |
4P | W | 450 | 1750 | 2300 | |
Resistance of each pole | Fixed type | μΩ | 11 | 9 | - |
Draw out type | μΩ | 20 | 14 | 10 | |
Dimensions (L×W×H) | 3P fixed type | mm | 362×323×402 | 422×323×402 | |
3P draw out type | mm | 375×461×452 | 435×471×452 | ||
4P fixed type | mm | 457×323×402 | 537×323×402 | ||
4P draw out type | mm | 470×461×452 | 550×471×452 | ||
Approximate weight | 3P fixed type | kg | 41 | 55 | |
3P draw out type | kg | 71 | 95 | 245 | |
4P fixed type | kg | 51.5 | 65 | - | |
4P draw out type | kg | 86 | 115 | 260 |
Overload protection data
Overload protection | YCW1-2000~6300 | ||||||
Adjust scope Ir1 | (0.4-1)In (pole difference 2%) | ||||||
1.05 Ir1 | h | ≥2h non-tripping | |||||
1.3 Ir1 | h | ≤1h tripping | |||||
1.5 Ir1 | s | 15 | 30 | 60 | 120 | 240 | 480 |
2.0 Ir1 | s | 8.4 | 16.9 | 33.7 | 67.5 | 135 | 270 |
Accuracy | % | ±15 |
Short circuit, short time delay | ||
Adjust scope Ir1 Ir2 | (0.4-15)In (pole difference 2%) | |
Delay time tr2 | ms | 100, 200, 300, 400 |
Accuracy | % | ±15 |
Short circuit, instantaneous | ||||
YCW1-2000 | YCW1-3200 | YCW1-6300 | ||
Adjust scope Ir1 Ir3 | 1In-50kA | 1In-75kA | 1In-100kA | |
Accuracy | % | ±15 | ±15 | ±15 |
Load monitoring output | YCW1-2000~6300 | |
Load adjust scope Ic1 | (0.2-1)In (pole difference 2%) | |
Delay time tc1 | tr1×0.5 | |
Load adjust scope Ic2 | (0.2-1)In (pole difference 2%) | |
Delay time tc2 | tr1×0.25 (anti-time limit) | |
Accuracy | s | 60 (set time limit) |
% | ±10 |