Portable 5000A Current Transformer Test Bench

Get reliable Portable 5000A Current Transformer Test Bench at our factory. Find quality testing equipment for your transformer needs. Contact us today.
Request a Quote

PRODUCTS DETAILS

Basic Info.

Model NO.
GF106T
Keyword
Current Transformer Test Bench
Model
Portable PT Analyzer
GF106t
Instrument Transformer Test Bench
Accuracy
0.2%
Large Current Output
0-1000A
Overall Dimension (L x W x H) (mm)
400mm X 250mm X 250mm
Weight (Kg)
22
Voltage
0-2500V
Transport Package
Standard Export Wooden Box
Specification
400 x 250 x 250 
Trademark
GFUVE
Origin
Beijing, China
Production Capacity
1000pieces/Month

Product Description

GF106T Portable 5000A current transformer test bench


It is mainly used for field testing of P class CT and PT. The test items mainly include excitation characteristic, transformation ratio, polarity, degauss, 5% and 10% error curves, secondary circuit check, withstand test of power frequency alternating current and secondary load. Adopting LCD, self-equipped mini type printer supporting field printing; supporting to use USB flash disk to dump data, with simple and convenient operation.

Electrical Current Potential Transformer Test Bench Price With Test Report Printer Kv Tester , Find Complete Details about Electrical Current Potential Transformer Test Bench Price With Test Report Printer Kv Tester,Kv Tester,Electrical Test Bench Price,Current Potential Transformer Test Bench With Test Report Printer from Testing Equipment Supplier.
Testing of current transformer includes: insulation resistance, polarity, burden, magnetization curve, turns ratio and primary injection test
Portable 5000A Current Transformer Test Bench



Main functions
I. Current Transformer (CT) II. Voltage Transformer (PT)
1. Magnetization curve 1. Excitation characteristic test
2. Transformation ratio test 2. Transformation ratio test
3. Polarity 3. Polarity 
4. 5% and 10% error curve 4. Withstand test of power frequency alternating current
5. Current Injecting 5. Degauss
6. Degauss 6. Calculation of knee point value
7. Withstand test of power frequency alternating   current 7. Actual secondary load test
8. Automatic calculation of excitation knee
point value
8. Resistance test
9. Actual secondary load test
10. Resistance test
Parameters
Electrical parameters
Accuracy 0.2%, 0.5%
Power supply AC 220V±10% or AC 110V±10%, 50/60Hz
Excitation voltage output 0-2500Vrms, 
Excitation current output 0-5Arms (20A peak-value)
Large current output 0-1000A
Electrical parameters - continued
Accuracy ≤0.5% (0.2%RD+0.3%RG)
Secondary winding DC resistance measurement Range 0.1-300Ω
Accuracy ≤0.5% (0.2%RD+0.3%RG)
Secondary actual load measurement Range 5VA-1000VA
Accuracy ≤0.5% (0.2%RD+0.3%RG)±0.1VA
CT/PT phase error measurement Accuracy ±4min
Resolution 0.01min
CT ratio error measurement Range ≤25000A/5A(5000A/1A)
Accuracy ≤0.5%
PT ratio error measurement Range 1-500KV
Accuracy ≤0.5%
Standards
Reference standards GB1207-2006, GB1208-2006, GB16847-1997
IEC60044-1, IEC60044-6, IEC61869-2-2012
Safety standards GB 4793.1-2007
EMC EMC standard 89/336/EEC
FCC Subpart B of Part 15 Class A
IEC 1000-4-2 /3 /4 /6
Mechanical parameters
Overall dimension (L x W x H) (mm) 400 x 250 x 250 
Weight (kg)   ≤22
Environmental conditions
Relative humidity    90RH%
Operating temperature -10°C to +40°C
Altitude ≤1000m

Photo
Portable 5000A Current Transformer Test Bench
 

Contact us

Please feel free to give your inquiry in the form below We will reply you in 24 hours