Basic Info.
Model NO.
GF106T
Keyword
Current Transformer Test Bench
Model
Portable PT Analyzer
GF106t
Instrument Transformer Test Bench
Accuracy
0.2%
Large Current Output
0-1000A
Overall Dimension (L x W x H) (mm)
400mm X 250mm X 250mm
Weight (Kg)
22
Voltage
0-2500V
Transport Package
Standard Export Wooden Box
Specification
400 x 250 x 250
Trademark
GFUVE
Origin
Beijing, China
Production Capacity
1000pieces/Month
Product Description
GF106T Portable 5000A current transformer test bench
It is mainly used for field testing of P class CT and PT. The test items mainly include excitation characteristic, transformation ratio, polarity, degauss, 5% and 10% error curves, secondary circuit check, withstand test of power frequency alternating current and secondary load. Adopting LCD, self-equipped mini type printer supporting field printing; supporting to use USB flash disk to dump data, with simple and convenient operation.
Electrical Current Potential Transformer Test Bench Price With Test Report Printer Kv Tester , Find Complete Details about Electrical Current Potential Transformer Test Bench Price With Test Report Printer Kv Tester,Kv Tester,Electrical Test Bench Price,Current Potential Transformer Test Bench With Test Report Printer from Testing Equipment Supplier.
Testing of current transformer includes: insulation resistance, polarity, burden, magnetization curve, turns ratio and primary injection test
Main functions
Parameters
Photo
It is mainly used for field testing of P class CT and PT. The test items mainly include excitation characteristic, transformation ratio, polarity, degauss, 5% and 10% error curves, secondary circuit check, withstand test of power frequency alternating current and secondary load. Adopting LCD, self-equipped mini type printer supporting field printing; supporting to use USB flash disk to dump data, with simple and convenient operation.
Electrical Current Potential Transformer Test Bench Price With Test Report Printer Kv Tester , Find Complete Details about Electrical Current Potential Transformer Test Bench Price With Test Report Printer Kv Tester,Kv Tester,Electrical Test Bench Price,Current Potential Transformer Test Bench With Test Report Printer from Testing Equipment Supplier.
Testing of current transformer includes: insulation resistance, polarity, burden, magnetization curve, turns ratio and primary injection test
Main functions
I. Current Transformer (CT) | II. Voltage Transformer (PT) |
---|---|
1. Magnetization curve | 1. Excitation characteristic test |
2. Transformation ratio test | 2. Transformation ratio test |
3. Polarity | 3. Polarity |
4. 5% and 10% error curve | 4. Withstand test of power frequency alternating current |
5. Current Injecting | 5. Degauss |
6. Degauss | 6. Calculation of knee point value |
7. Withstand test of power frequency alternating current | 7. Actual secondary load test |
8. Automatic calculation of excitation knee point value | 8. Resistance test |
9. Actual secondary load test | |
10. Resistance test |
Electrical parameters | ||
---|---|---|
Accuracy | 0.2%, 0.5% | |
Power supply | AC 220V±10% or AC 110V±10%, 50/60Hz | |
Excitation voltage output | 0-2500Vrms, | |
Excitation current output | 0-5Arms (20A peak-value) | |
Large current output | 0-1000A | |
Electrical parameters - continued | ||
Accuracy | ≤0.5% (0.2%RD+0.3%RG) | |
Secondary winding DC resistance measurement | Range | 0.1-300Ω |
Accuracy | ≤0.5% (0.2%RD+0.3%RG) | |
Secondary actual load measurement | Range | 5VA-1000VA |
Accuracy | ≤0.5% (0.2%RD+0.3%RG)±0.1VA | |
CT/PT phase error measurement | Accuracy | ±4min |
Resolution | 0.01min | |
CT ratio error measurement | Range | ≤25000A/5A(5000A/1A) |
Accuracy | ≤0.5% | |
PT ratio error measurement | Range | 1-500KV |
Accuracy | ≤0.5% | |
Standards | ||
Reference standards | GB1207-2006, GB1208-2006, GB16847-1997 IEC60044-1, IEC60044-6, IEC61869-2-2012 | |
Safety standards | GB 4793.1-2007 | |
EMC | EMC standard 89/336/EEC | |
FCC Subpart B of Part 15 Class A | ||
IEC 1000-4-2 /3 /4 /6 | ||
Mechanical parameters | ||
Overall dimension (L x W x H) (mm) | 400 x 250 x 250 | |
Weight (kg) | ≤22 | |
Environmental conditions | ||
Relative humidity | 90RH% | |
Operating temperature | -10°C to +40°C | |
Altitude | ≤1000m |
Photo