S9-M-30-2000kVA Distribution Transformer 2000kVA Power Transformer/10kv Power Trasnformer Substation

S9-M-30-2000kVA Distribution Transformer 2000kVA Power Transformer/10kv Power Transformer Substation. We are a factory specializing in high-quality power transformers.
Request a Quote

PRODUCTS DETAILS

Basic Info.

Model NO.
S9-M-30-2000kVA
Cooling Method
Oil-immersed Type Transformer, Oil-Immersed Type Transformer
Winding Type
Customized, Customized
Certification
ISO9001-2000, ISO9001, ISO9001-2000, ISO9001, ISO9001-2000, ISO9001
Usage
Single-phase Transformer, Rectifier Transformer, Combined Transformer, Power Transformer, Distribution Transformer, Single-Phase Transformer, Rectifier Transformer, Combined Transformer, Power Transformer, Distribution Transformer, Single-Phase Transformer, Rectifier Transformer, Combined Transformer, Power Transformer, Distribution Transformer
Frequency Characteristics
50Hz 60Hz, 50Hz 60Hz
Shape of Core
Ring, Ring
Brand
Ville, Ville
LV
0.4
Hv
6 6.3 10 10.5 11
Tapping
± 5% or ± 2X2.5%
Transport Package
wooden case or as per requirement
Specification
ISO 9001:2000
Trademark
VILLE
Origin
China
HS Code
8504319000
Production Capacity
50,000 set/year

Product Description

General:
Different from normal type, S9 - M -30 -2000KVA Three phase oil-immersed transformer is cooled by the
corrugated plate of tank without conservator. It is applicable to 10kV, 50Hz power transmission and distribution
system for power supply and lighting in industrial and agricultural field.

Feature:
1. Energy saved:
    Compared with old type S7, no-load loss decreases 10.25% averagely and on-load current decreases
    37.9%, which means 18.39% operation cost is reduced.
2. Long-term reliable service life:
    Fully enclosed transformer tank and rim shall be bolted together or welded firmly. Isolation between oil and air
    keeps insulation away from moisture, which lowers
    insulation aging and improves service life.
3. Free from untanking:
    Free from untanking before operation, so its cost is saved.
4. Free from maintenance
5. Low noise:
    Impacted structure in design, new material and new technology adopted and low noise.
6. Small size and artistic appearance:
    Owing to the corrugated plate used for radiation, oil volume is changed by adjustment and compensation
    through expansion and shrinkage of corrugated plate when the temperature of oil is changed. Corrugated
    tank is small size in good looking.

Technical parameters:
Model
 
Rated Voltage 
(kVA)
Voltage Combination Vector Group Po 
(w)
Pk 
(w)
Io 
(%)
Uk 
(%)
Soud 
Level 
(dB)
HV (kv) Tapping LV (kv)
S9-M-30/10
 
30
 
6
 
6.3
 
10
 
10.5
 
11
 
 
± 5%
or ± 2x2.5%
 
0.4
 
Y,yn0 
or
D,yn11
 
130
 
600
 
2.1
 
4.0
 
44
 
S9-M-50/10
 
50
 
170
 
870
 
2.0
 
S9-M-63/10
 
63
 
200
 
1040
 
1.9
 
S9-M-80/10
 
80
 
250
 
1250
 
1.8
 
48
 
S9-M-100/10
 
100
 
290
 
1500
 
1.6
 
S9-M-125/10
 
125
 
340
 
1800
 
1.5
 
49
 
S9-M-160/10
 
160
 
400
 
2200
 
1.4
 
S9-M-200/10
 
200
 
480
 
2600
 
1.3
 
51
 
S9-M-250/10
 
250
 
560
 
3050
 
1.2
 
S9-M-315/10
 
315
 
670
 
3650
 
1.1
 
53
 
S9-M-400/10
 
400
 
800
 
4300
 
1.0
 
S9-M-500/10
 
500
 
960
 
5150
 
1.0
 
55
 
S9-M-630/10
 
630
 
1200
 
6200
 
0.9
 
4.5
 
S9-M-800/10
 
800
 
1400
 
7500
 
0.8
 
57
 
S9-M-1000/10
 
1000
 
1700
 
10300
 
0.7
 
S9-M-1250/10
 
1250
 
1950
 
12000
 
0.6
 
59
 
S9-M-1600/10
 
1600
 
2400
 
14500
 
0.6
 
S9-M-2000/10
 
2000
 
2520
 
17820
 
0.6
 

Reference:
S9-M-30-2000kVA Distribution Transformer 2000kVA Power Transformer/10kv Power Trasnformer Substation
S9-M-30-2000kVA Distribution Transformer 2000kVA Power Transformer/10kv Power Trasnformer Substation S9-M-30-2000kVA Distribution Transformer 2000kVA Power Transformer/10kv Power Trasnformer Substation

Our Services

1.

Pre sale service

a.

make technical solution

b.

send quotation, technical data sheet and drawing

c.

prepare power transmission plan, testing plan and shipment plan

2.

In sale service

a.

supervise the manufacturing schedule totally in accordance with the plan

b.

send photos to customer during every manufacturing process(hold point)

c.

inform the customer one week before testing.

3.

After sale service

a.

installation and commissioning, training the workers

b.

quick response within 12 hours any time

c.

provide 12 months guarantee period normally.


 

Contact us

Please feel free to give your inquiry in the form below We will reply you in 24 hours