- Overview
- Product Parameters
Basic Info.
Model NO.
S13-M(R)
Cooling Method
Oil-immersed Type Transformer
Winding Type
Two-winding Transformer
Certification
ISO9001, CCC
Usage
Combined Transformer, Power Transformer, Distribution Transformer
Frequency Characteristics
Power Frequency
Shape of Core
Ring
Brand
Bo Lian
Product Name
Oil-Immersed Transformer
Connection Group
Dyn11 / Yyn0
Coil Material
Aluminum/Copper
Rated Capacity
30/1600kVA
High Pressure/Low Pressure
0.4/11kv
Transformer Type
S11 Oil-Immersed Transformer;
Frequency
50/60Hz
Transport Package
Wooden Pallet, Wooden Case
Specification
1600× 920× 1550
Trademark
BO LIAN
Origin
China
Packaging & Delivery
Package Size
1650.00cm * 930.00cm * 1640.00cm
Package Gross Weight
2530.000kg
Product Description
Product characteristics:
1.The core is made of high quality cold rolled grain oriented silicon steel sheet, 45°three-stage fully oblique seams, no punching, and the core column is brushed with polyurethane varnish for curing.
2.The coil is made of oxygen-free copper conductor with reasonable structure, which improves the resistance to sudden short-circuit.
3.Increase the effective support of winding end face, so that the short-circuit resistance of the winding is further improved.
4.Oil storage cabinet is cancelled, and the wave fin of corrugated oil tank replaces the oil pipe as the cooling element, the wave super can expand and contract with the volume expansion and contraction of the transformer oil, the transformer oil is isolated from the atmosphere, which prevents and reduces the deterioration of the oil quality and the insulation dampness, and strengthens the operation reliability, and the normal operation is free of maintenance.
1.The core is made of high quality cold rolled grain oriented silicon steel sheet, 45°three-stage fully oblique seams, no punching, and the core column is brushed with polyurethane varnish for curing.
2.The coil is made of oxygen-free copper conductor with reasonable structure, which improves the resistance to sudden short-circuit.
3.Increase the effective support of winding end face, so that the short-circuit resistance of the winding is further improved.
4.Oil storage cabinet is cancelled, and the wave fin of corrugated oil tank replaces the oil pipe as the cooling element, the wave super can expand and contract with the volume expansion and contraction of the transformer oil, the transformer oil is isolated from the atmosphere, which prevents and reduces the deterioration of the oil quality and the insulation dampness, and strengthens the operation reliability, and the normal operation is free of maintenance.
Number of Phase | Three Phase |
Winding Type | Two Winding |
Rated Capacity | 50/2500kVA |
High Voltage | 10/11kV |
Low Voltage | 0.4kV |
Tapping Range | ±2x2.5% |
Impedance Voltage | 4% |
Load Loss | 2.73/2.6kW |
No-load Loss | 0.34kW |
No-load Current | 1.0% |
Frequency | 50/60Hz |
Connection Group | Yyn0/Dyn11 |
Cooling Method | ONAN |
Coil Material | Aluminum/Copper |
Size | Based on customization |
Weight | kg |