- Overview
- Product Description
- Product Parameters
- Company Profile
- Competitive Products
- Certifications
- Customer Visit
- On-site Service
- Package and Delivery
Basic Info.
Product Description
DC high voltage generator is mainly used in the electric power department, power department of industrial and mining, metallurgy, iron and steel enterprise for zinc oxide lightning arrester, power cables, transformers, circuit breakers, generators and other high voltage electrical equipment of DC withstand voltage test or DC leakage current test.
1. the case is portable and convenient to carry.2. Using AIPWM technology, adjusts the PWM inaccuracy linearity make the accuracy is greatly improved. The ripple coefficient is less than 1%.
3. AI zinc oxide arrester and oil immersed transformer measuring function can directly save experiment report, and the accuracy is less than 1%. Keep manual 0.75 UDC1mA.
4. Used the AI technology screen setting over-voltage protection and over-current protection to replace the digital dial switch only can set voltage value, cannot set current value and voltage drift problem. Error of 1% or less.
5. The full measuring range smoothly adjust pressure, voltage regulation accuracy is less than 1%, stability is less than 1%, the voltage current error is less than 0.5%±1 letter.
6. with total time T1 and segmented time T2, and any voltage, current chronograph function.
7. The instrument added the calendar and time function.
Specification Technology parameter | 60/2 | 120/2 | 200/2 | 300/5 |
Output Voltage (kV) | 60 | 120 | 200 | 300 |
Output Current (mA) | 2 | 2 | 2 | 5 |
Output power (W) | 120 | 240 | 400 | 1500 |
Charging Current (mA) | 3 | 3 | 5 | 5 |
Controll Case Weight(kg) | 10.1 | 13 | 13.1 | 13.1 |
Double voltage cylinder weight(kg) | 2.3 | 3.2 | 8.0 | 10 |
Double voltage cylinder specification(mm) | Ф90 340 | Ф90 470 | Ф110 910 | Ф110 1200 |
Voltage Measurement Error | ±1% | |||
Current Measurement Error | ±0.5% | |||
Over-voltage Setting Error | AI technique setting over-voltage and over-current protection. Error ≤±1% | |||
0.75 Switch Error | 0.75UDC-1mA high precision single touch button(accurancy≤±1%)is much suitable for zinc oxide arrester test. | |||
Ripper Coefficient | ≤±1% | |||
Working Method | Intermittent use: rated load for 30 minutes 1.1 times rated voltage use: 10 minutes | |||
Working Environment | Temperature:-10ºC~+40ºC | |||
Relatived Humidity:When the room temperature is 25 ºC is not greater than 85% (no lon) | ||||
Altitude: below 1500 meters | ||||
Capacitive Load | Tested product capacity no restriction | |||
Structure Features | Electrical insulation double voltage cylinder | |||
Air insulation, no leakage |
Wuhan Hezhong Electric Equipment Manufacture Co., Ltd is a high-tech enterprise professionally engaged in R & D, manufacture and marketing of power testing products, instruments, power industry automation systems for 20 years.We export completed set to Korea, Singapore, Vietnam, India, Ecuador, Paraguay, Pakistan, Philippines, Russia, Italy, Austria, Portugal, Chile such as PD test system, impulse voltage generator, temperature rising test system, transformer comprehensive test system, cable fault detect system and varies of instruments for transformer, circuit breaker, switchgear, lightning arrestor, insulator, cable, battery,SF6 gas and so on.